การปฏิบัติตามรหัส: เอทิลีนออกไซด์ (ETO)

A Comprehensive Guide for Sterilization & Fumigation Facilities

1. Receiving and Unloading Procedures

Compliance with subsection 14.2 is mandatory for both full and empty ETO containers.

Safety Checkpoints

  • Vehicle engines must be OFF, brakes set, and wheels chocked.
  • No smoking or open flames within 25 ft (7.62 m)-
  • Containers must be kept UPRIGHT at all times.

Handling Prohibitions

  • NO Stacking: Containers must never be stacked or rolled.
  • Forklift Safety: Do not lift drums by placing forks under chime rings.

2. Storage Standards

Indoor Storage Limit: The maximum quantity of ETO in a sterilization building is 10,000 lb (4536 kg)-

Indoor Areas

  • Classified for ignition source control (Class I, Div 2).
  • Spot heating limit: 125°F (51.7°C)-

Outdoor Areas

  • 25% of perimeter must be open to atmosphere.
  • Clear of dry vegetation for 15 ft (4.6 m)-
  • Provide protection from vehicle damage.

3. Piping Systems & Gas Dispensing

All metallic piping must comply with ASME B31.3 (Process Piping) and have a minimum melting point of 1500°F (815.6°C)-

? Critical Gas Detection: Indoor dispensing areas must have a continuous gas detection system. Alarms must trigger when levels exceed 25% of the LFL (7500 ppm)-

Ventilation Rate

Mechanical ventilation must operate continuously at no less than 1 scf/min•ft² of floor area.

Shutoff Valves

Each system requires two remotely operated shutoff valves. The first must be within 5 ft (1.5 m) of the container.

4. Disposal and Emission Control

Compliance with Section 14.9 ensures environmental safety and effective ETO neutralization.

Wet Scrubbers

Must be designed so solution cannot enter process lines. Pure liquid ETO must never feed directly into gas-treatment scrubbers.

Catalytic Converters

Must include automatic shutdown if temperature exceeds catalyst supplier limits.

BOCON Compliance Solution: To meet California’s stringent emission standards, our EO Scrubber Systems are engineered to provide maximum neutralization efficiency, preventing any solution backflow and maintaining 25% LFL safety interlocks.

5. Construction & Fire Safety

  • Explosion Venting: Structures must have non-combustible construction and explosion control per Section 6.10.
  • Fire Suppression: ETO storage areas must be protected by a Deluge System in accordance with NFPA 16.
  • Bonding: All piping must be bonded to an earth ground to control static electricity.

Ensure Your Facility Meets California Safety Codes

From ASME-certified ETO sterilizers to advanced EO Scrubber systems, BOCON provides the technology you need for safe, compliant, and efficient operations.